Myers MSP50 Submersible Sewage Pump Description

The Myers MSP50 Submersible Sewage Pump is specifically designed to meet the demands of handling wastewater and sewage in residential and commercial building applications. The 2" NPT discharge pump (3" discharge optional) is available with a powerful 1/2 horsepower motor, in both automatic and manual configurations and can handle capacities up to 150 gallons per minute and heads up to 29 feet.

Myers MSP50 Submersible Sewage Pump Typical Application

  • Commercial Sewage
  • Residential Sewage
  • High-Capacity Sump
  • Septic Tank Effluent

Myers MSP50 Submersible Sewage Pump Features

  • Water-Resistant Power Cord with Molded Plug is Available in 10 or 20 Foot Lengths and is Easily Field Serviceable.
  • Oil-Filled Motor Provides Superior Cooling and Permanent Lubrication of Bearings Minimizing Maintenance and Extending Service Life.
  • Powerful 1/2 HP Motor Provides Cool and Quiet Operation. Motor Windings Contain Automatic Thermal Overload Protection.
  • The High-Capacity, Non-Clog, Cast Iron Impeller, Which is Threaded to a Nickel Plated Steel Shaft, Efficiently Handles up to 1-1/2" Spherical Solids. Pump-Out Vanes on Back of Impeller Prevent Stringy Materials from Binding Impeller or Shaft.
  • Upper Radial and Lower Thrust Bearings are Heavy-Duty, Single-Row Ball Bearings that are Permanently Lubricated for Service-Free Life.
  • Heavy-Duty, Cast Iron Construction Provides Long Life and Assists in Heat Dissipation for Cooler Motor Operation.
  • Precision, Mechanical Shaft Seal is Extensively-Lapped, Carbon Ceramic-Faced for a Long Leakproof Life.
  • Bottom Inlet has no Screen to Become Clogged, Providing Optimum Pump Performance and Minimal Maintenance.
  • Discharge is a Standard 2" NPT (3" is optional)
  • Does not Include "Piggyback" Diaphragm Switch

Specifications

Myers MSP50M1 Submersible Sewage PumpTechnical Details

  • VOLTAGE: 1ø, 115V, 60Hz
  • HORSEPOWER: 0.5 HP
  • AMP DRAW (full load): 12.0
  • MOTOR TYPE: Split-Phase
  • RPM: 1750
  • MAXIMUM HEAD: up to 28'
  • MAXIMUM CAPACITY: up to 140 GPM
  • SWITCH TYPE: Manual
  • DISCHARGE PIPE SIZE: 2.0" NPT
  • MAXIMUM SOLIDS HANDLING SIZE: 1-1/2"
  • IMPELLER TYPE: Cast Iron, Non-Clogging
  • CORD LENGTH: 10'
  • CORD SIZE: 16/3; Type:STWA
  • BODY CONSTRUCTION: Cast Iron
  • MAXIMUM LIQUID TEMPERATURE: 104°F (40C)

Myers MSP50 Submersible Sewage Pump Performance Curve


WARNING Cancer and Reproductive Harm - www.P65Warnings.ca.gov WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Resources

Myers MSP50 Submersible Sewage Pump Product Resources

product-resourcesb.png

Download Myers MSP50 Sales Brochure

Download Myers MSP50 Installation & Service Manual

Warranty

Loading...

Video

View full details

PUMPS, WATER & WASTE WATER TREATMENT AND A WHOLE LOT MORE

Dedicated to deliver the highest quality products, and services in the water and wastewater industry, and with the help of our well-trained staff, provide a lasting value to each customer we support... read more

HELPING CUSTOMERS SINCE 1953

As time-tested specialists in water and waste water pumping systems, we are your best choice for pumps and related equipment.

  • Wastewater Treatment Systems
  • Sump Pump Systems
  • UV Water Purification & Treatment
  • Irrigation Pump Systems
  • Storm Water Lift Stations
  • Water Well Pump Systems

OUR CUSTOMERS REVIEWS