Littelfuse PC-105 Five-Channel Pump Controller Product Specifications
Supply Voltage . . . . . . . . . . . . 120 VAC
Frequency . . . . . . . . . . . . 50*/60Hz
Probe Sense Voltage . . . . . . . . . 5vdc continuous
Relay Output Rating
- 2 Form C Isolated. . . . . . . . . . . . . . . . . . .480VA @ 240VAC, B300 Pilot Duty
- . . . . . . . . . . . . . . . . . . . . . 7A @ 240VAC General Purpose
Temperature Range . . . . . . . . . . . . . . . . . . . . . -20° to 55°C (-4° to 131°F)
Maximum Input Power . . . . . . . . . . . . . . . . . . . . . 4 W
Wire Range . . . . . . . . . . . . . . . . . . . . . . . .12-20 AWG
Terminal Torque . . . . . . . . . . . . . . . . . . . . . . . .4.5 in.-lbs
Pump In-Rush Delay . . . . . . . . . . . . . 2 seconds
Electrostatic Discharge (ESD) . . . . . . . . . IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity (RFI) . . . . . . . . . IEC 61000-4-3, Level 3, 10V/m
Fast Transients . . . . . . . . . IEC 61000-4-4, Level 3, 4kV input power 2kV inputs/outputs
Safety Mark
- UL . . . . . . . . . . . . . . . . . . . . . . . UL508 (File #E68520)
Weight . . . . . . . . . . . . . . . . . . . . . . . . 19.2 oz.
Mounting Method . . . . . . . . . . . 35mm DIN rail or Surface Mount (#6 or #8 screws)
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov