Littelfuse 355-400-5 Voltage Monitor Specifications
3-Phase Line Voltage . . . . . . . . . . . . 380 to 480 VAC
Frequency
. . . . . . . . . . . . . . . . . . . . . 50*/60Hz
Low Voltage (% of setpoint)
- Trip . . . . . . . . . . . . . . . . . . . . . . . . . . 90% ±1%
- Reset . . . . . . . . . . . . . . . . . . . . . . . . . 93% ±1%
High Voltage (% of setpoint)
- Trip . . . . . . . . . . . . . . . . . . . . . . . . . . 110% ±1%
- Reset . . . . . . . . . . . . . . . . . . . . . . . . . 107% ±1%
Voltage Unbalance (NEMA)
- Trip . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8% adjustable
- Reset . . . . . . . . . . . . . . . . . . . . . . . . . Trip setting minus 1%
Trip Delay Time
- Low & High Voltage and Unbalance. . . . . . . . . . . . 2-30 seconds adjustable
- Single-Phasing Faults (>25% UB) . . . . . . . 2 seconds
Restart Delay Time
- After a Fault . . . . . . . . . . . . . . . . . Manual, 2-300 seconds adj.
- After a Complete Power Loss. . . . . . . Manual, 2-300 seconds adj.
Output Contact Rating
- SPDT (355200) . . . . . . . . . . . . . . . . . . . . . . . . 480VA @ 240VAC Pilot Duty
- . . . . . . . . . . . . . . . . . . . . . . . . . . . . or 10A General Purpose
- SPDT (355400, 355600) . . . . . . . . . . . . 470VA @ 600VAC Pilot Duty
- DPDT(-5 Option) . . . . . . . . . . . . . . . . . 470VA @ 600VAC Pilot Duty
Temperature Range
- Operating . . . . . . . . . . . . . . . . . -40° to 70°C (-40° to 158°F)
- Storage . . . . . . . -40° to 80°C (-40° to 176°F)
Repeat Accuracy
- Fixed Conditions . . . . . . . . . . . . . . . . . ±0.1%
Power Consumption
. . . . . . . . . . . . . 6 Watts (Max.)
Terminal Torque . . . . . . 7 in.-lbs.
Wire Size . . . . . . 12-18AWG
Transient Protection (Internal) . . . . . . 2500V for 10 ms
UL Recognized . . . . . . UL508 (File #E68520)
Weight . . . . . . . . . . . . . . . . . . . . . . . . 15.4 oz.
Mounting Method
. . . . . . . . . . . #8 screws
Special Options
*Note: 50Hz will increase all delay timers by 20%.