Blue Ribbon BCP3000 Description
The BCP3000 Surge Protector is designed to assist in the prevention of
damage to the BC001 Birdcage Submersible Level Transmitter from damaging
voltage and current surges.
Blue Ribbon BCP3000 Typical Applications
- Surge Protection for BC001 Birdcage Level Transmitter
Blue Ribbon BCP3000 Features
- Protection from damaging voltage and current surges
- Din-rail mount, pluggable surge protector
- Remote failure indication
- Indicator Light
Blue Ribbon BCP3000 Specifications
- Power: 24VDC
- IEC Category / EN Type: C1/C2/C3/D1
- Highest Continuous Voltage Uc: DC/AC 28V/20V
- Lightning Test Current limp: Per Path 2.5kA
- Nominal Current lN: 450 MA
- Nom Discharge surge current (8/20) μs: Core-Core 10ka Core-Ground
10kA
- Total Surge Current (8-20) μs: 20kA
- Output voltage Limitation at 1 kV/ μs: Core-Core ≤40V Core-Ground
≤450V
- Residual Voltage at ln: Core-Core ≤40V
- Response Time tA: Core-Core ≤1ns
- Resistance per Path: 2.2 Ω
- Insulation Test Voltage: 500VDC
- Auxiliary Voltage UN: 8VDC .38VDC, P≤0.8W
- Auxiliary Power: 1A max
- Temperature Range: -40°C – 85°C
- Protection: IP20
- Test Standard: IEC61643 / DIN EN 61643-21
- Remote Indication Contact: N/C Contact
- Maximum Operating Voltage: 250 VAC
- Maximum Operating Current: 0.2A (250 VAC) / 0.2a(VDC)
- Dimensions: 99Hx17.5Wx90H mm
WARNING:
Cancer and Reproductive Harm - www.P65Warnings.ca.gov